Name of File 3825-56-08.pdf cached at 15/12/2017 17:59:07 - with 7 pages. pdfPath: E:\k9.istructe.org\CMS\webtest\files\ae\ae7342cd-adca-44e0-9468-c8f25e163386.pdf. thumbPath: E:\k9.istructe.org\CMS\webtest\files\pdfthumbs\ae7342cd-adca-44e0-9468-c8f25e163386_1.png. objDoc: 1 - True. objPreview.Log: . strFileName: ae7342cd-adca-44e0-9468-c8f25e163386_1.png

Members/subscribers must be logged in to view this article

Correspondence on A Limit State Design Method for the Tension Region of Bolted Beam-Column Connections by J.A. Packer and L.J. Morris

The authors' examination of end plate connections, with particular reference to thin column flanges, provides reassuring evidence of the ductility of such connections, albeit with some loss of strength. The criteria adopted for assessing the yield moment in the tests seem unduly conservative when one considers the well-formed plateaux of the moment-rotation curves. For double beam connections in a multi-storey frame, it would not be unreasonable to anticipate hinge rotations of the order of 30 x 10-3 radian and on this basis J1 almost qualifies as a full-strength connection instead of the half-strength assessment applied by the authors. J.O. Surtees, J.H. Howlett and R.C. Hairsine